海底盾构隧道双层衬砌结构联合承载力学特性研究

Study on the Combined Bearing Mechanical Characteristics of the Double-layer Lining Structure of Subsea Shield Tunnels

  • 摘要: 为探究海底盾构隧道双层衬砌结构承载特性,以甬舟高速公路复线金塘海底隧道为工程背景,考虑双层衬砌界面黏结损伤力学效应,建立盾构隧道双层衬砌结构三维弹塑性损伤模型,研究高水压条件下管片结构与二次衬砌联合承载力学特性,明确双层衬砌结构安全承载状态。研究结果表明:(1)与单层管片方案相比,双层衬砌叠合结构极限承载力与结构刚度分别提升66.3%、200.8%,复合式衬砌结构承载力及横向刚度提升较小,仅分别提升7.1%与16.9%。界面黏结强度损失越大,隧道结构极限承载力越低,隧道适应变形能力越差。(2)在叠合结构承载过程中,管片及二次衬砌结构均存在超出极限承载力的风险。二次衬砌拱底呈现小偏心受拉状态,该处极易产生贯穿裂缝;二次衬砌拱腰呈现小偏心受压状态,该处易发生压溃破坏;复合结构管片及二次衬砌均呈现大偏心受压状态,结构无贯穿裂缝产生,但结构裂缝宽度存在超出规范限值的风险。(3)基于叠合结构二次衬砌变形破坏特征及复合结构剩余承载力指标,提出盾构隧道双层衬砌结构安全控制指标。

     

    Abstract: In order to explore the bearing characteristics of the double-layer lining structure of subsea shield tun? nels, taking the Jintang Subsea Tunnel on Ningbo-Zhoushan Expressway 2nd as an engineering background, this study considers the bond damage mechanics effect at the interface of the double-layer lining. A three-dimensional elastoplastic damage model for the double-layer lining structure of shield tunnels is established to study the com? bined bearing mechanical characteristics of the tunnel segment structure and secondary lining under high water pressure conditions, and to clarify the safe bearing state of the double-layer lining structure. The research results show that: (1) Compared with the single-layer segment scheme, the ultimate bearing capacity and structural stiffness of the overlapped double-layer lining structure increase by 66.3% and 200.8%, respectively, while the composite lining has little impact on its structural bearing capacity and lateral stiffness, with increases of only 7.1% and 16.9%, respectively. The greater the loss of interface bond strength, the lower the ultimate bearing capacity of the tunnel structure and the worse its deformation adaptability; (2) During the bearing process of the overlapping struc? ture, both the tunnel segment and the secondary lining structure are at risk of exceeding their ultimate bearing ca? pacity. The arch bottom of secondary lining presents a small eccentric tensile state, where through cracks are likely to occur; the arch waist of secondary lining presents a small eccentric compressive state, where crush failure is like? ly; the segment and secondary lining of the composite structure both show a large eccentric compressive state, and no through cracks are generated, but there is a risk that the width of structural cracks may exceed the code limits; (3) Based on the deformation failure characteristics of the secondary lining of the overlapping structure and the residual bearing capacity index of the composite structure, safety control indicators for the double-layer lining structure of shield tunnels are proposed.

     

/

返回文章
返回